Solution 6000 - Hardwired Fire/Smoke Detector

Modified on Fri, 8 Jan, 2021 at 10:50 AM

By default, Output 3 on Solution 6000 is designed for Smoke Detector

The Event Type for Output 3 is Smoke Sensor GND


This Output is used to allow Smoke Detectors to be automatically reset when the system is disarmed. You should connect the GND terminal of all Smoke Detectors in the system to Outputs which are set to this event type.


For this Output type to perform correctly you should program the Output polarity as type 11 - Normally Low One Shot Open and program the Output time parameter to be 5 seconds.


If the Smoke Detector needs to be connected to a Zone input, please set the Zone Type to 24-Hour Fire.


If Fire Alarm Verification is required, we recommend that you program the zone pulse count to 2 pulses and the pulse count time to 90 seconds for each fire zone.