Fault Analysis - Communication Fail/Receiver 3 & 4 Fail

Modified on Mon, 4 Mar, 2019 at 12:01 PM

Some installers may encounter strange Faults for Communication Fail for Receiver 3 or Receiver 4 while they do not have Receiver 3 or Receiver in the system. 



Please follow below steps to trouble shoot these faults:


(1) check the Transmission Format for Receiver 3 (Location: 1450) and Receiver 4 (Location: 1490) and make sure they are "0 - Not used";

(2) if you install IP module (B426-M) or 3G GPRS module (B450-M + B443) in the system, please check the IP module or 3G GPRS module and make sure the Jumper is NOT on MODE - you should not see the BLUE led;


(3) if you only have one IP module, please do not enable cloud connection for IP module 2 - location 82 and location 7456.


After that, please do arm/disarm to configure the panel. Or you may need to do a power cycle on your panel.


Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article